Auto tranfer switchboard





Features
Parameters
Dimensions
Download catalogue
* ATS maintenance operations of load when the power grid off  by mode automatically switches to the generator from the grid. ATS auto start / stop the generator, and automatically transfer generator and power grid. When the grid voltage has ensure the normal value, the load automatically connect to the grid.
* There are two operating modes manually or automatically compared with the traditional design facilitates inspection and operation.
* Using the smart controller transfer from Zelio Logic 20/12/26 I / O, with the clock , processing time and response fast , on-site programming or computer connection , communication modules MOBUS available , clear display
* Associated mechanical and electrical interlock between ACB or MCCB each other to ensure safety and prevent from incorrect operation.
* Always bring you peace of mind with comprehensive system protection: overload, short circuit, over voltage, low voltage
* Ability to integrate with MSB system and  power factor regulator to improve the flexibility of the system with multiple sources, multiple generators, the load priority.
* Always give clients comprehensive solutions for system operation and remote control through the use of the PLC controller from prestigious companies such as Schneider, Siemens, Mitsubishi ...
* With modular and removable devices,  the installation and maintenance easily and quickly.
* Always give clients comprehensive solutions for system operation and remote control through the use of the PLC controller prestigious companies such as Schneider , Siemens , Mitsubishi ...
* With modular devices and removable should the installation and maintenance easy and quick

Standard IEC 61439-1 ; ISO 9001:2008
Creepage distances and clearances Rated impulse withstand voltage (Uimp)
Overvoltage category
Pollution degree
8kV
III
3
Rated insulation voltage (Ui)
1000V
Rated operational voltage (Ue)

Up to 690V
Rated current (In) Rated current Up to 6300A
Busbar (3-poles and 4-poles) Rated peak withstand current (Ipk)
Rated short-time withstand current (Icw)
Up to 187kA
Up to 100kA/1s; 80kA/3s
Surface treatment Frame, Enclosure, Doors

Internal subdivisions
Tole 2mm galvanized/electrostatic powder-coated
Tole 1mm galvanized
Form
1 to 4b
Degree of protection
IP2X to IP54

Dimensions
Height (mm) 2000, 2200, 2400
Width (mm) 600, 700, 800, 900, 1000, 1100, 1200
Depth (mm) 600, 800, 1000, 1200



Logout